6. Resistance
Thermometers – Measuring Circuit
Temperature measurement by means of resistance thermometers
uses resistance detectors, in which the temperature dependence of the resistor is
known and defined in standards. Predominantly platinum
(and, to a much lesser extent, nickel) resistors, whose electrical
resistance value increases with the rising temperature, due
to the positive temperature coefficience, are used
in industrial measurement technology. Unlike the voltage-generating
thermocouple assembly, a resistor does not provide any
electrical energy, meaning that (external) energy is supplied through an electrical measuring
circuit. A constant current source, which generates a voltage drop
proportional to the resistance at the resistance detector,
is usually used to provide
this.
6.1 Schematic Diagrams
Figure 4 shows the possible connection techniques for resistance
thermometers

|
|

|
| |
|
|
2–wire circuit |
|
2-wire circuit with loop |
| |
|
|

|
|


|
| |
|
|
|
3-wire circuit |
|
4-wire circuit |
| |
|
|
|
a. Resistance detector b. Inner conductor (inner
cable): Connection between resistance detector and connection point c.
Connection point: Junction of inner conductors and connection cable d.
Connection cable (copper cable): Connection between resistance thermometer and
measuring equipment e. Measuring equipment and constant current source:
Measurement of the voltage drop (U, U1, U2) above the resistance detector
through which there is a constant current
flow.
|
6.2 Connection Techniques:
Figure 4 shows the possible connection techniques for
resistance thermometers, making a division into two-wire, three-wire and
four-wire circuits. The two-wire circuit connects the resistance detector to the
measuring equipment through a two-wire cable. The existing lead resistances which are connected in series
to the resistance detector cause a higher total
resistance and hence some significant measurement errors. For
this reason, (cable) compensation is also required here. As the lead
resistances change additionally depends on temperature, the two-wire circuit
is only suitable for simple measurements. The two-wire circuit with
loop provides a variant to the simple two-wire circuit. Provided that
all four leads have the same properties and
are exposed to the same temperatures, the lead
resistances can be measured under operational conditions
via the loop and compensated accordingly. Instead
of this connection variant, however, current industrial measurement technology makes
almost exclusive use of the three-wire circuit described
below. With the three-wire circuit, an additional cable
is carried to the measuring equipment from a connection contact
of the resistance detector, giving rise to
two measuring circuits. Provided that the resistances of
all three leads are the same, the influence
of the cable resistance is compensated, in current standard measuring equipment with a
three-wire input, by a corresponding internal connection technique. No cable
compensation is required here. In the case of
the four-wire circuit, if the cable resistances
of the four leads differ, then they are also
compensated. The voltage drop "U" above the resistance detector through
which there is a constant current flow undergoes high-impedance tapping here
via two measuring cables. Provided that the
input/ inner resistance of the (voltage) measuring equipment
is a multiple of the cable resistance,
no significant measurement error occurs. For this reason, the
four-wire circuit is used for temperature measurements that require
particularly high measurement precision.
Go to Section 7
(Configuration of Resistance Thermometers) |